Lightning Monitoring Box

Lightning Monitoring Box

The intelligent lightning monitoring box is used for real-time monitoring of lightning strikes and lightning flow in lightning rods and down conductors. It adopts temperature-controlled circuit breakertechnology and built-in over-current protection circuit to completely avoid fire hazards and displays the power supply status

*The price of the product is determined by the volume of your order. We always try to provide our customers with unique discounts and delivery times for their order.
  • DESCRIPTION
  • SPECIFICATION
  • TECHNICAL & SALES SUPPORT

Lightning Monitoring Box Features

The intelligent lightning monitoring box is used for real-time monitoring of lightning strikes and lightning flow in lightning rods and down conductors. It adopts temperature-controlled circuit breakertechnology and built-in over-current protection circuit to completely avoid fire hazards and displays the power supply status.

Easy To Install And Simple To Maintain

The technology is exquisite and can work for a long time in harsh environments such as acid, alkali, dust, salt spray and moisture.
Monitor lightning information (number of lightning strikes, peak value, polarity, Q value, specificenergy, time), ambient temperature and humidity for collection and data upload. Equipped with a 10-inch LCD touch screen, all parameters are intuitive and clear, and equipped with various alarm information Ethernet Interface, MODBUS-TCP standard protocol.

Environmental Terminal Technical Parameters

NameDescribe
Communication InterfaceR5485Bit rate 9600; parity bit N; data bit 8; stop bit 1
TemperatureConnect to the COM2 port of the touch screen and set the address to 3
Humidity-40-100℃ 土 1°C
carbon monoxide0-100%RH 土 3%
0-1000ppm 土 5%

Lightning Monitoring Box Technical Parameters

namedescribe
Communication InterfaceRS485MODBUSRTU protocol
Baud rate 9600; parity bit N; data bit 8; stop bit 1
Connect to the COM2 port of the touch screen and set the address to 1
Remote signal collection channelT01 is for SPD remote signaling on Channel I; T02 is for SPD remote signaling on Channel II; T03 is for backup remote signaling on Channel I; T04 is for backup remote signaling on Channel II
lightning strike collection channelRecord the number of lightning strikes, polarity, peak size, lightning strike occurrence date/time, the maximum count is 9999 times
Trigger current: 0.5/1/2.5/5kA optional, default is 5kA
Resolution: 0.lkA
Collection frequency: 10 times/second
Surgetype:Tl
SensorMicro Rogowski coil, collection range 0.5-lOOkA
Interface protectionserial portSet up surge protection circuit, 4000V lightning protection
Shell materialABS, gray, flame retardant VO
Working environment -40~85℃,0~95%RH